Sitemap  Search  Contact 

Optical Phase Conductor

Separators 245kV for OPPC


Type: S H P
Characteristics :
Tension, Um 245 kV
Pollution class (IEC60815) II IV  
ID-number 05K4225/A 05K4168/A  
Number of sheds 25 47  
Creepage 4900 7640 mm
Arcing distance, min. 1840 1940 mm
Dry lightning withstand voltage 1050 kV
Wet power frequency withstand voltage 460 kV
Total height, type S & P 2730 2830 mm
Total height, type H 2827.5 2927.5 mm
Weight (appr.), type S 56 62 kg
Weight (appr.), type H 52 58 kg
Weight (appr.), type P 55 61 kg
Fixing eye, diameter 20 mm
Fixing eye, width 16 or 19 mm
Steel tube, diameter 2.5 - 3.5 mm
Approach cable, diameter 11.5 - 18 mm
OPPC, diameter 10.0 - 28.0 mm
OPPC entries 1 or 2  
Approach cable entries 1 - 4  
Number of splices with FiberArt™ module 144 "crimp" splice protectors or 72 heat-shrinkable splice protectors  

Dimensions, base plate [mm] : Naming : SEP-X-YYYY-NN-ZZZ
Thickness [mm] : 15
X Type:
S Standing upright
H hanging
P hanging, fixed on base plate
YYYY ID-number
NN Pollution class
ZZZ Tenseion, Um

 
 
 
 
 

top